EasyManua.ls Logo

Micom P634 - Page 827

Micom P634
840 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Version Changes
  ‑308
  ‑407/408
  ‑622-724
Release: 2012-02-01
No changes.
Diagram
No changes.
Software
IEC
Bug fixing:
If single-pole signals of function group SIG_1 were
active during device startup, this could lead to an
aborted initialization of the Ethernet
communication module.
During the process of connection with clients that
use the “IntegrityPeriod” option, sporadically the
MMS communication of the Ethernet
communication module would crash without an
internal monitoring response to re-establish the
functionality. (GOOSE messaging and other
communication tasks were not affected.)
Reports of events could get lost if too many state
changes occurred in a short period of time,
especially during secondary injection testing.
If clients did connect to the device immediately
after completion of Ethernet communication
module startup, this could lead to the temporary
erroneous reporting of default values for the
external device status (DEVxx) and of the single-
pole signals (SIG_1).
GOOSE The GOOSE Time Allowed to Live (TAL) supervision is
enhanced with respect to simultaneous state changes
of multiple GOOSE messages.
PC, COMM2
Bug fixing:
If clients did connect to the device immediately
after startup of the Ethernet communication
module, the initialization of the second internal
communication interface could remain
incomplete. As a consequence, access by the
operating program via the COMM2 interface or by
tunneling was not possible in this case.
P634
  ‑308
  ‑407/408
  ‑630-725
Release: 2012-02-01
Hardware
A5 P634 Version History P634
P634/EN M/R-42-A // P634311653 A5-27

Table of Contents

Related product manuals