Version Changes
IEC The number of clients for a report has been increased:
An unbuffered report (urcbA … urcbP) can be allocated
to max. 8 clients (previously: 1), and a buffered report
(brcbA … brcbH) can be allocated to max. 4 clients
(previously: 1).
OUTP Bug notice: With version P63x -650 the test operation
of output relays can be executed independent from the
off-line state of the device!
MAIN The previously available parameters (003 039) MAIN:
Warm restart und (000 085) MAIN: Cold restart
have been relabeled MAIN: Soft Warm restart and
MAIN: Soft Cold restart, respectively. They still
trigger a restart of the device, but now the hardware
tests are not carried out anymore during the startup
phase. (This way the restart needs less time.)
For a restart including hardware tests, the following
new parameters can now be used:
●
(010 166) MAIN: Warm restart
●
(009 254) MAIN: Cold restart
LOG_2 There is a new function group LOG_2 (Programmable
Logic 2). It is identical to the previously available
function group LOGIC, but it offers only four logical
equations. These, however, have long-term timers,
settable from 0 to 60000 s (= 16 hours, 40 minutes).
P634
‑310
‑409/410
‑631
Release: 2013-11-18
Hardware
No changes.
Diagram
No changes.
Software
This release of the Transformer Differential
Protection Device MiCOM P634 has been certified
by the KEMA.
COMM1 The following two parameters were without function for
the P634 (because of the absence of control
functionality), so that they have now been removed:
●
(221 105) COMM1: Sel. pos. dev.test
●
(221 106) COMM1: Test position dev.
P634
‑310
‑409/410
‑650-701
Hardware
No changes.
Diagram
A5 P634 Version History P634
P634/EN M/R-42-A // P634‑311‑653 A5-31