Version Changes
P634
  ‑310
  ‑409/410
  ‑650-703
Release: 2014-09-16
Hardware
No changes.
Diagram
No changes.
Software
No changes.
P634
  ‑310
  ‑409/410
  ‑651
Release: 2015-02-20
Hardware
No changes.
Diagram
No changes.
Software
FT_RC
Bug fixing:
The fault recording triggers (016 018) FT_RC:
Id> and (016 019) FT_RC: IR> were not
operating correctly. This has now been corrected.
PC, COMM1,
COMM2
Bug fixing:
When reading the list of stored fault recordings
according to the IEC 60870-5-103
communications protocol (with the operating
program), the additional binary information
“Recording with tripping” and “Recording
triggered by starting” are now correctly
transmitted.
IEC
Bug fixing:
Disabling the protection via binary input ((003
026) MAIN: Disable protect. EXT = Yes) could
have interrupted the IEC 61850 communication
permanently. This has now been corrected.
OUTP
Bug fixing:
Latched outputs were not reset when executing a
general reset. This has now been corrected.
DIFF Implementation of a binary input signal for blocking the
differential protection function:
(003 163) DIFF: Blocking EXT