18 - 70
18.4 Error Code and Error Message Lists
18.4.3 Actions by error messages
18
TROUBLESHOOTING
Table18.23 Error messages on MELSECNET/H utility (Continued)
Error message Corrective action
The setting value for the maximum number of transients for one
station is greater than the setting value for the maximum number of
transients in one scan.
Please input values so that the setting value for the maximum
number of transients for one station is ( the maximum number of
transients in 1 scan.
Make setting so that the maximum No. of transients for one station is
equal to or less than the maximum No. of transients in 1 scan.
The setting value for the maximum number of transients for one
station is outside the range.
Please input a value within the range 1-10.
Set the maximum No. of transients for one station within the range of
1 to 10.
The setting value for the maximum number of transients in one scan
is outside the range.
Please input a value within the range 1-255.
Set the maximum No. of transients in 1 scan within the range of 1 to
255.
The setting value for the number of equally assigned points assigned
is outside the range.
Please input a value within the range XX-YY.
Set the points of equal assignment within the range of XX to YY.
The specified file cannot be read because the MELSECNET/H utility
version is different.
Install the same MELSECNET/H utility version as the one used to
create the file.
The specified file is not a parameter file of the MELSECNET/H utility. Check the specified file.
The specified station No. is set as the I/O master station.
Please erase the I/O master station and set the reserved station.
Cancel the I/O master station setting and set the reserved station
status.
The start device No. setting value is outside the range.
Please input the value within the range XX-YY.
Set the start device No. within the range of XX to YY.
The start I/O No. is not set.
Please input the start I/O No. with in the range of 0-0EF0.
Set the start I/O No. within the range of 0 to 0FE0.
The station number setting value is outside the range.
Please input a value within the range 1-64.
Set the station No. within the range of 1 to 64.
The system timer is not set.
Please set the system timer.
Set the system timer.
The target CPU No. setting value is outside the range.
Please input the value within the range 1-4.
Set the target CPU No. within the range of 1 to 4.
The total for B, W and Y exceeds the 2000 bytes which is the
ordinary total for one station.
Please set the settings so that the total for B, W and Y does not
exceed the 2000 byte ordinary total for one station.
Correct the setting so that the total bytes of B, W, and Y allocated to
a normal station does not exceed 2000.
The total number of linked stations setting value is outside the range.
Please input the value within the range 2-64.
Set the total number of linked stations with the range of 2 to 64.
The total of low speed LB, low speed LW allocated to a normal
station exceeds 2000 bytes.
Please set the allocations of low speed LB & LW not exceeding 2000
bytes.
Correct the setting so that the total bytes of low speed LB and low
speed LW allocated to a normal station does not exceed 2000.
The year setting is out of range.
Please input with in the range of 2000-2099.
Set a year value of the system timer within the range of 2000 to
2099.
Two or more stations are selected for the I/O master station set/
erase station No.
Please select 1 station for the I/O master station set/erase station
No.
Select one station No., and press the Specify I/O master station
button.
Unable to obtain the write authority.
Verify the user name and password.
• Confirm the user name and password, and connect again.
(
Section 5.11.2)
• Connect without write authority.
Unable to open the specified file.
Check the specified file.
Set the total of the saving location and file names using 128
characters or less.