EasyManuals Logo

Omron NX Series User Manual

Omron NX Series
464 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #259 background imageLoading...
Page #259 background image
3. Status Details of the EtherNet/IP Port
Bit Name Description
0 Owned Indicates when the EtherNet/IP port has an open connection as the target of
a tag data link.
1 Reserved Always FALSE.
2 Configured Tag data link settings exist.
3 Reserved Always FALSE.
4 to 7 Extended Device Status
Indicates the status of the EtherNet/IP port.
*1
8 Minor Recoverable Fault TRUE when any of the following errors occurs.
IP Router T
able Setting Error
T
ag Data Link Setting Error
Tag Data Link Timeout
Tag Data Link Connection Timeout
FTP Server Setting Error
SNMP Setting Error
Tag Name Resolution Error
9 Minor Unrecoverable Fault TRUE when the following error occurs.
Identity Error
10 Major Recoverable Fault TRUE when any of the following errors occurs.
IP Address Duplication Error
BOOTP Server Error
Basic Ethernet Setting Error
IP Address Setting Error
11 Major Unrecoverable Fault TRUE when any of the following errors occurs.
Communications Controller Error
MAC Address Error
12 to 15 Reserved Always FALSE.
*1. Bits 7 to 4 indicate the status of the EtherNet/IP port.
b7 b6 b5 b4
0 1 0 1 A major fault occurred.
0 0 1 0 A timeout occurred in one or more target connections.
0 0 1 1 Indicates that there are no tag data link settings.
0 1 1 0 Indicates that one or more connections are performing communications
normally.
0
1 1 1 Other than the above.
Request Paths (IOIs) to Specify Objects
When you specify an object, specify the request path (IOI) for each service code as given below.
Service code Class ID Instance ID Attribute ID
01 hex Get_Attribute_All 01 hex
Specifying a service for a class
: 00 hex
Specifying a service for an in-
stance
: Always 01 hex
Not required.
0E hex Get_Attribute_Single
Reading a class attribute
: 01 or 02 hex
Reading an instance attribute
: 01 to 07 hex
05 hex Reset Always 01 hex Not required.
10 CIP Message Communications
10-31
NX-series EtherNet/IP Unit User's Manual (W627)
10-5 CIP Object Services
10
10-5-2 Identity Object (Class ID: 01 hex)

Table of Contents

Other manuals for Omron NX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX Series and is the answer not in the manual?

Omron NX Series Specifications

General IconGeneral
Programming LanguagesLadder, Structured Text, Function Block Diagram, Sequential Function Chart
Communication PortsEthernet, USB, RS-232C, RS-485
Memory CapacityVaries by model
Program MemoryVaries by model
Data MemoryVaries by model
Operating Temperature0°C to 55°C
Power Supply24 VDC
Ethernet Ports1 or 2 ports (depending on model)
USB Ports1 or 2 ports (depending on model)
DimensionsVaries by model
WeightVaries by model

Related product manuals