CIP Safety on EtherNet/IP Compatible
Combined with the NX-SL5£££ Safety Control Unit, you can build a system which uses CIP
Safety on EtherNet/IP communications in networks between Controllers and field networks. Safety
communications by CIP Safety is enabled with devices that support CIP Safety on EtherNet/IP and
other Safety CPU Units.
Precautions for Correct Use
An NX-series EtherNet/IP Unit is required to perform CIP Safety communications. The built-in
EtherNet/IP port on an NX502 CPU Unit does not support the CIP Safety communications.
CIP Safety communications and tag data links cannot be used together in one NX-series
EtherNet/IP Unit.
The I/O refresh time varies depending on the number of connections for CIP Safety commu-
nications. Check the effect of the number of connections for CIP Safety communications on
the task execution time.
l
LLDP
The LLDP (Link Layer Discovery Protocol) enables to exchange information with other network de-
vices that are connected to a physically communicable range.
1 Features and System Configuration
1-5
NX-series EtherNet/IP Unit User's Manual (W627)
1-1 Features
1
1-1-2 Features of NX-series EtherNet/IP Units

Table of Contents