EasyManua.ls Logo

Panasonic MN101L Series

Panasonic MN101L Series
563 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4
Clock/ Mode/ Voltage Control
Voltage Control IV - 29
4.3.4 Operation
Voltage Transition of VDD18 by Program
Figure:4.3.1 shows the example of voltage transition of VDD18 by program.
When SLOW mode, the PWCTR0.VDDLV1-0 are set to change the output voltage, VDD18 and achieve low-
power consumption or high-speed operation depending on the operating frequency.
Voltage transition cannot be set in NORMAL mode. It is also impossible to change the voltage from 1.3 V to 1.8
V and from 1.8 V to 1.3 V. After updating the PWCTR0.VDDLV1-0, CPU clock is halted for the time set in the
PWCTR1.PWUPTM2-0 while the voltage is boosted during i) and iii) shown in the Figure:4.3.1. Although CPU
clock is not halted while the voltage is stepped down during ii) and iv) shown in the Figure:4.3.1, it does not affect
the operation.
Figure:4.3.1 Voltage Transition of VDD18 by Program
The setting example to change VDD18 from 1.1 V to 1.8 V at iii) in Figure:4.3.1 is shown below.
CPU outage in voltage transition: 32/f
SCLK
(f
SCLK
= 32.768 kHz, 977 µs)
..
Be sure to execute the setting in SLOW mode.
..
Step Setting Register name Description
1
Set CPU outage in voltage transition
PWCTR1
Set PWUPTM2-0 to "011".
2 Set output voltage, VDD18 PWCTR0 Set VDDLV1-0 to "10".
3 NOP instruction - Insert 3 NOP instructions.
4 Transition to NORMAL mode CPUM Set to "00000111".
1.1 V 1.3 V 1.1 V
VDD30
10 MHz
M
AX operating speed
Power ON
40 kHz 40 kHz
40 kHz
VDD30
VDD18 output voltage
VDD18 output
1.8 V
Operating mode
SLOW
NORMAL SLOW
i)
ii)
iii) iv)
1 MHz
1.8 V 1.1 V
SLOW NORMAL
1.3 V
1.1 V
00 01 00
VDDLV1-0
10
00
CPU idle time
CPU idle time

Table of Contents

Related product manuals