Trips & Fault Finding 10-7
AC30 series Variable Speed Inverter
HEXADECIMAL REPRESENTATION OF TRIPS
Each trip has a unique, eight-digit hexadecimal number as shown in the tables below. This number is referred to as the trip mask. The trip masks
are used in the Enable, Active and Warnings parameters in the Trips module.
ID
Trip Name
Mask
User
Disable
1
OVER VOLTAGE
00000001
2
UNDER VOLTAGE
00000002
3
OVER CURRENT
00000004
4
STACK FAULT
00000008
5
STACK OVER CURRENT
00000010
6
CURRENT LIMIT
00000020
7
MOTOR STALL
00000040
8
INVERSE TIME
00000080
9
MOTOR I2T
00000100
10
LOW SPEED I
00000200
11
HEATSINK OVERTEMP
00000400
12
AMBIENT OVERTEMP
00000800
13
MOTOR OVERTEMP
00001000
14
EXTERNAL TRIP
00002000
15
BRAKE SHORT CCT
00004000
16
BRAKE RESISTOR
00008000
17
BRAKE SWITCH
00010000
18
LOCAL CONTROL
00020000
19
COMMS BREAK
00040000
20
LINE CONTACTOR
00080000
21
PHASE FAIL
00100000
22
VDC RIPPLE
00200000
ID
Trip Name
Mask
User
Disable
23
BASE MODBUS BREAK
00400000
24
24V OVERLOAD
00800000
25
PMAC SPEED ERROR
01000000
26
OVERSPEED
02000000
27
SAFE TORQUE OFF
04000000
28
FEEDBACK MISSING
08000000
31
POWER LOSS STOP
40000000
32
SPEED SENSOR FAULT
80000000
33
A1
00000001*
34
A2
00000002*
35
A3
00000004*
36
A4
00000008*
37
A5
00000010*
38
A6
00000020*
39
A7
00000040*
40
A8
00000080*
41
SPEED ERROR FAULT
00000100*
42
PEER TO PEER OVERRUN
00000200*
43
PHASE CONFIG
00000400*
* These masks apply to parameter words “33 – 64