EasyManua.ls Logo

Parker AC30 - Supply Short Circuit Rating

Parker AC30
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F-19 Technical Specifications
AC30 series Variable Speed Drive
SUPPLY SHORT CIRCUIT RATING
The following drives when fitted with UL Listed fuses are suitable for use on a circuit capable of delivering not more than:
Frames D, E, F, G: 5,000 RMS Symmetrical Amperes, 480V maximum
Frame H & J: 10,000 RMS Symmetrical Amperes, 480V maximum
Frame K: 18,000 RMS Symmetrical Amperes, 480V maximum
Refer to Appendix C: “Compliance Solid State Short Circuit Protection
When group installed with the specified line reactor frame D, E, F, G, H, J & K sizes may be used on a supply rating delivering not more than 50,000
RMS Symmetrical amperes, 480V maximum, see table below for further information:
Frame Size
Motor Power
Parker Part Number
MTE Part Number
Inductance mH
Rated amps
D
1.1kW / 1.5hp
CO470651
RL-00402
6.5
4
D
1.5kW / 2hp
CO470651
RL-00402
6.5
4
D
2.2kW / 3hp
CO352782
RL-00803
5
8
D
3kW
CO352782
RL-00803
5
8
D
4kW / 5hp
CO470652
RL-00802
3
8
D
5.5kW / 7.5hp
CO352783
RL-01202
2.5
12
E
7.5kW / 10hp
CO352785
RL-01802
1.5
18
E
11kW / 15hp
CO352786
RL-02502
1.2
25
F
15kW / 20hp
CO352901
RL-03502
0.8
35
F
18kW / 25hp
CO352901
RL-03502
0.8
35
G
22kW / 30hp
CO352902
RL-04502
0.7
45
G
30kW / 40hp
CO352903
RL-05502
0.5
55
G
37kW / 50hp
CO352904
RL-08002
0.4
80
H
45kW / 60hp
CO352904
RL-08002
0.4
80
H
55kW / 75hp
CO352905
RL-10002
0.3
100
H
75kW / 100hp
CO352906
RL-13002
0.2
130
J
90kW / 125hp
CO470057
RL-16002
0.15
160
J
110kW / 150hp
CO470045
RL-20002
0.11
200
J
132kW / 200hp
CO470046
RL-25002
0.09
250
K
160kW / 250hp
CO470047
RL-32002
0.075
320
K
200kW / 300hp
CO470048
RL-40002
0.06
400
K
250kW / 350hp
CO470049
RL-50002
0.05
500
380-480V