12-21 Ethernet
AC30 series Variable Speed Inverters
PTP PARAMETER SUMMARY
Note: The value of the PTP configuration parameters only become active when the PTP module initialises, i.e. on inverter power-up, on transition
of the parameter 1661 PTP Enable to TRUE or connection of one or more Ethernet cables.
Parameter Name
No.
Path
Default
Range
Units
Writable
PTP Enable
1661
Setup::Communications::PTP
Parameters::Base Comms::PTP
FALSE
FALSE
TRUE
ALWAYS
PTP parameter.
Enables the precision time protocol.
PTP Clock Type
1684
Setup::Communications::PTP
Parameters::Base Comms::PTP
0: MASTER OR SLAVE
0:MASTER OR SLAVE
1:SLAVE ONLY
ALWAYS
PTP parameter
Sets if the inverter can become a master or slave clock, or a slave clock only.
Enumerated values:
0: MASTER OR SLAVE - the device clock will become a Master if it is determined to be the best master in a network,
otherwise it will become a Slave
1: SLAVE ONLY - the device clock can only become a Slave
PTP Clock Mode
1683
Setup::Communications::PTP
Parameters::Base Comms::PTP
0:E2E
0:E2E
ALWAYS
PTP parameter.
Sets the PTP clock mode to either end-to-end (E2E) or peer-to-peer (P2P). See description in section Advanced Users for more
details. Note that currently E2E is only available.
Enumerated values:
0: E2E
PTP Log Sync Interval
1681
Setup::Communications::PTP
Parameters::Base Comms::PTP
-1
-1 to
0
ALWAYS
PTP parameter.
Sets the Log Sync Interval. See description in section Advanced Configuration for more details. This parameter should be set to
the same value on all inverters using PTP.