F-15 Technical Specifications
AC30 series Variable Speed Drive
LINE INPUT FUSE RATINGS (EUROPE)
Product Code
Input Fuse Rating (A)
Product Code
Input Fuse Rating (A)
NORMAL DUTY
NORMAL DUTY
400V BUILD VARIANT 380-480V ±10%, 50/60Hz +5%*
Frame D
Frame G
31x-4D0004…
10A
31x-4G0045
63A
31x-4D0005…
10A
31x-4G0060
80A
31x-4D0006…
10A
31x-4G0073
100A
31x-4D0008…
10A
Frame H
31x-4D0010…
12A
31x-4H0087
125A
31x-4D0012…
16A
31x-4H0105
150A
Frame E
31x-4H0145
200A
31x-4E0016…
20A
Frame J
31x-4E0023…
25A
31x-4J0180
250A
Frame F
31x-4J0205
315A
31x-4F0032…
32A
31x-4J0260
400A
31x-4F0038…
40A
Frame K
31x-4K0315
400A
31x-4K0380
500A
31x-4K0440
630A
Type: Semiconductor protection fuses 500V AC, Mersen type A50QSX or equivalent.

Table of Contents

Other manuals for Parker AC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 and is the answer not in the manual?

Parker AC30 Specifications

General IconGeneral
Protection RatingIP20
SeriesAC30
TypeVariable Frequency Drive
Overload Capacity150% for 60 seconds
Cooling MethodFan Cooled
Communication ProtocolsCANopen
Power Range0.75 to 250 kW (1 to 350 hp)
Switching Frequency2kHz to 16kHz
SafetySafe Torque Off (STO)
Output CurrentModel Dependent
Power Rating0.75 to 250 kW (1 to 350 hp)
Efficiency>97%
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit, overheating
DimensionsModel Dependent
WeightModel Dependent
Operating Temperature-10°C to +40°C
Output Voltage0 to Input Voltage