Technical Specifications F-14
AC30 series Variable Speed Drive
Power Supply = 510V - 650V DC Average
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Product Code
Motor Power
Output Current
(A)
Input Current
(A)
Estimated
Efficiency
Switching Frequency
(kHz)
nominal / maximum
Output Current Derate %/kHz
(applied above nominal switching
frequency)
FRAME J : Input currents for kW ratings are at 530V DC input and for Hp ratings at 620V DC input, with AC line choke equivalent to 4%
Normal Duty (Output Overload Motoring 110% for 60s)
34x-4J0180…
90kW
180
198
98%
2.5 / 8
8.1%
125Hp
156
180
34x-4J0205…
110kW
205
243
98%
2.5 / 8
8.4%
150Hp
180
214
34x-4J0260…
132kW
260
289
98%
2.5 / 8
8.7%
200Hp
240
283
Heavy Duty (Output Overload Motoring 150% for 60s, 180% for 3s short term rating)
34x-4J0180…
75kW
145
168
98%
2.5 / 8
7.5%
100Hp
124
146
34x-4J0205…
90kW
180
201
98%
2.5 / 8
8.6%
125Hp
156
181
34x-4J0260…
110kW
205
244
98%
2.5 / 8
8.0%
150Hp
180
217