EasyManua.ls Logo

Parker AC30 - Minimum Speed

Parker AC30
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-98 Parameter Reference
AC30 series Variable Speed Drive
Minimum Speed
Setup::Application::Minimum Speed
Function availability depends on macro selected.
The minimum speed function is used to determine how the AC30V will follow a reference.
Parameter Name
No.
Path
Default
Range
Units
Writable
Minimum Speed Value
1906
Setup::Application::Minimum Speed
-100.0
-100.0 to 100.0
%
ALWAYS
Specifies the minimum output value.
Minimum Speed Mode
1907
Setup::Application::Minimum Speed
0
0:PROP WITH MINIMUM
1:LINEAR
ALWAYS
There are two modes of operation.
Functional Description
Min
0 100%
100
-100
input
output
There are two operating modes for the MINIMUM SPEED function:
PROP WITH MINIMUM (proportional with minimum)
In this mode the MINIMUM SPEED function behaves like a simple clamp. The Minimum Speed Value has the valid range -100% to 100% and the
output is always greater than or equal to the Minimum Speed Value.
LINEAR
In this mode the MINIMUM SPEED function first clamps the input to zero then rescales the input such that the output goes linearly between
minimum and 100% for an input that goes from 0 to 100%.
Note the constraints:-
min >= 0
input >= 0
max = 100%

Table of Contents