D-78 Parameter Reference
AC30 series Variable Speed Drive
Flycatching
Parameters::Motor Control::Flycatching
Only available if IM MOTOR selected in Control Mode
This feature performs a directional speed search. It allows the Drive to seamlessly catch a spinning motor before controlling the motor to the desired
setpoint. This is especially useful for large inertia fan loads, where drafts in building air ducts can cause a fan to `windmill’.
Parameters::Motor Control::Flycatching
Enable flycatching in V/Hz control mode when TRUE
Parameters::Motor Control::Flycatching
Enable flycatching in Vector control mode when TRUE
Parameters::Motor Control::Flycatching
0:ALWAYS
1:TRIP OR POWER UP
2:TRIP
Mode of operation - V/Hz control
Parameters::Motor Control::Flycatching
0:BIDIRECTIONAL
1:UNIDIRECTION
The type of speed search carried out by the flycatching sequence.
Parameters::Motor Control::Flycatching
Only under VHz control
The percentage level of the search volts applied to the motor during the speed search phase of the flycatching sequence. Increasing
this parameter improves the accuracy of the discovered motor speed but increases the braking influence of the speed search on the
rotating motor.