D-36 Parameter Reference
AC30 series Variable Speed Drive
Control Mode
Setup:: Motor Control::Control & Type:: Control Strategy
Parameters::Motor Control::Control & Type::Control Strategy
The control mode block provides the means for selecting the type of motor and the desired method of controlling the motor.
Setup::Motor Control::Control and Type
Setup::Regen Control
Parameters::Control Mode::Control
Mode
0:INDUCTION MOTOR
1:PMAC MOTOR
2:AFE
Motor type selection parameter
Allows the user to select the type of motor.
Setup::Motor Control::Control and
Type
Parameters::Control Mode::Control
Mode
0:VOLTS - HERTZ CONTROL
1:VECTOR CONTROL
This parameter will only become visible if an induction motor is selected. If a PMAC motor is selected, the Control Strategy will
automatically be set to Vector Control.
Select control strategy selection parameter.
Allows the user to select the method of controlling the motor.
Setup::Motor Control::Control and Type
Parameters::Control Mode::Control
Mode
0:SENSORLESS
1:ENCODER FEEDBACK
AC30V : This parameter will only become visible if an induction motor is selected, Control Strategy is set to Vector Control, and the
encoder option is fitted. If the encoder option is not fitted, the control strategy is forced to be sensorless.
AC30P/D: This parameter will only become visible if an induction motor is selected, Control Strategy is set to Vector Control. If the
encoder option is not fitted, selecting ENCODER FEEDBACK will give a trip.
This parameter allows selects between sensorless control, and control using encoder feedback.
If an encoder is available, encoder feedback control would normally be the preferred choice as it gives better speed control and higher
performance.