Technical Specifications F-4
AC30 series Variable Speed Drive
AC FED ELECTRICAL RATINGS (400V BUILD VARIANT)
Power Supply = 380-480V ±10%, 50/60Hz 5%
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Minimum repetitive power up / power down cycle time = 10 mins
Product Code
Motor Power
Output Current
(A)
Input Current
(A)
Estimated
Efficiency
Switching Frequency
(kHz)
nominal / maximum
Output Current Derate %/kHz
(applied above nominal switching
frequency)
FRAME D : Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit current
5kA.
Normal Duty (Output Overload Motoring 110% for 60s)
31x-4D0004…
1.1kW
3.5
4
95%
4 / 16
2.4%
1.5Hp
3.0
3.5
31x-4D0005…
1.5kW
4.5
5.3
96%
4 / 16
3.7%
2Hp
3.4
4.5
31x-4D0006…
2.2kW
5.5
7.6
97%
4 / 16
4.5%
3Hp
4.8
6.4
31x-4D0008…
3kW
7.5
6.5
97%
4 / 16
4.0%
31x-4D0010…
4kW
10.0
8.0
97%
4 / 16
3.9%
5Hp
7.6
6.6
31x-4D0012…
5.5kW
12.0
10.6
97%
4 / 16
3.5%
7.5Hp
11
9.4
Heavy Duty (Output Overload Motoring 150% for 60s, 180% for 3s short term rating)
31x-4D0004
0.75kW
2.5
2.9
95%
4 / 16
1.0%
1Hp
2.1
2.4
31x-4D0005
1.1kW
3.5
4.0
95%
4 / 16
3.1%
1.5Hp
3.0
3.5
31x-4D0006
1.5kW
4.5
5.3
96%
4 / 16
4.3%
2Hp
3.4
4.5
31x-4D0008
2.2kW
5.5
5.2
97%
4 / 16
3.8%
3Hp
4.8
4.6
31x-4D0010
3kW
7.5
6.5
97%
4 / 16
3.8%
31x-4D0012
4kW
10.0
8.0
97%
4 / 16
3.3%
5Hp
7.6
6.6

Table of Contents