D-42 Parameter Reference
AC30 series Variable Speed Drive
Current Sensor Trip
Parameters::Trips::Current Sensor Trip
This function contains parameters associated to the missing current sensor detection and trip condition
Parameter Name
No.
Path
Default
Range
Units
Writable
Current Diff Level
1658
Parameters::Trips::Current Sensor Trip
25.00
0.00 to 100.00
%
ALWAYS
The percentage of motor rated current which, if exceeded by difference between RMS values of two current sensor measurements,
causes this trip to become active. This trip detects missing, or broken connections in the current sensing circuitry that result in loss of
measurement of one sensor. Enabled in V/Hz mode of operation only.

Table of Contents

Other manuals for Parker AC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 and is the answer not in the manual?

Parker AC30 Specifications

General IconGeneral
Protection RatingIP20
SeriesAC30
TypeVariable Frequency Drive
Overload Capacity150% for 60 seconds
Cooling MethodFan Cooled
Communication ProtocolsCANopen
Power Range0.75 to 250 kW (1 to 350 hp)
Switching Frequency2kHz to 16kHz
SafetySafe Torque Off (STO)
Output CurrentModel Dependent
Power Rating0.75 to 250 kW (1 to 350 hp)
Efficiency>97%
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit, overheating
DimensionsModel Dependent
WeightModel Dependent
Operating Temperature-10°C to +40°C
Output Voltage0 to Input Voltage