12-25 Ethernet
AC30 series Variable Speed Inverters
PEER TO PEER PARAMETER SUMMARY
Note: The value of the Peer to Peer configuration parameters only become active when the Peer to Peer module initialises, i.e. on inverter power-
up or transition of the parameter 1725 Peer to Peer Enable to TRUE.
Setup::Communications::Peer to Peer
Parameters::Base Comms::Peer to Peer
Peer to Peer Parameter.
Enables the Peer to Peer module.
Setup::Communications::Peer to Peer
Parameters::Base Comms::Peer to Peer
0.0.0.0 to
255.255.255.255
Peer to Peer Parameter.
Sets the destination IP address of the data when the Peer to Peer module is sending. If the Destination IP Address is set to 255.255.255.255 then
the sent data is broadcast and all listening inverters will receive the data.
Setup::Communications::Peer to Peer
Parameters::Base Comms::Peer to Peer
Peer to Peer Parameter.
Sets the UDP port number the Peer to Peer module sends data to. Normally this will be set the same as the Local Port.
Setup::Communications::Peer to Peer
Parameters::Base Comms::Peer to Peer
Peer to Peer Parameter.
Sets the UDP port number the Peer to Peer module receives the data on. Normally this will be set the same as the Destination Port.
Monitor::Communications::Peer to Peer
Parameters::Base Comms::Peer to Peer
Peer to Peer Parameter.
A diagnostic parameter indicating the state of the Peer to Peer module.
Enumerated values:
0: DISABLED - the Peer to Peer module is disabled.
1: ACTIVE - the Peer to Peer module is enabled and ready for communications.
2: ERROR - the Peer to Peer module is in an error state and communications could not be established.