4-39 Installation
AC30 series Variable Speed Inverter
TERMINAL TIGHTENING TORQUES
Frame Size
Power Terminals
DC Bus Terminals
Brake Terminals
Ground Stud
Frame D
0.56-0.8Nm
(5-7 lb-in)
0.56-0.8Nm
(5-7 lb-in)
0.56-0.8Nm
(5-7 lb-in)
1.8Nm
(16 lb-in)
Frame E
0.56-0.8Nm
(5-7 lb-in)
0.56-0.8Nm
(5-7 lb-in)
0.56-0.8Nm
(5-7 lb-in)
1.8Nm
(16 lb-in)
Frame F
1.35Nm
(12 lb-in)
1.35Nm
(12 lb-in)
1.35Nm
(12 lb-in)
1.8Nm
(16 lb-in)
Frame G
* 1.35Nm or 2.0Nm
(12 lb-in or 18 lb-in)
2.0Nm
(18 lb-in)
2.0Nm
(18 lb-in)
3.6Nm
(32 lb-in)
Frame H
20Nm Max.
(177 lb-in)
20Nm Max.
(177 lb-in)
2.0Nm
(18 lb-in)
20Nm Max.
(177 lb-in)
Frame J
20Nm Max.
(177 lb-in)
20Nm Max.
(177 lb-in)
20Nm Max.
(177 lb-in)
20Nm Max.
(177 lb-in)
Frame K
38Nm Max.
(336 lb-in)
38Nm Max.
(336 lb-in)
38Nm Max.
(336 lb-in)
20Nm Max.
(177 lb-in)
* Cream power terminals 2.0Nm (18 lb-in)
Black power terminals 1.35Nm (12 lb-in)
OPTIONAL EQUIPMENT
Refer to Chapter 5 Associated Equipment.
BRAKE WIRING
Refer to Chapter 5 Associated Equipment on wiring details.