Parameter Reference D-117
AC30 series Variable Speed Drive
PMAC Motor Data
Setup::Motor Control::MotorData PMAC
Parameters::Motor Control::PMAC Motor Data
Only available if PMAC Motor selected in Control Mode.
The PMAC Motor Data contains the parameters needed to run and control of a PMAC motor. A PMAC motor is a Permanent Magnet AC Motor with
sinusoidal back EMF.
Parameter Name
No.
Path
Default
Range
Units
Writable
PMAC Max Speed
0555
Setup::Motor Control::Motor Data PMAC
Parameters::Motor Control::PMAC Motor
Data
3000
0 to 100000
RPM
ALWAYS
Set the motor’s rated speed in rpm.
PMAC Max Current
0556
Same as PNO 555
4.50
0.00 to 5000.00
A
ALWAYS
Set the motor’s maximum current ( Amps rms ).
PMAC Rated Current
0557
Same as PNO 555
4.50
0.00 to 5000.00
A
ALWAYS
Set the motor’s rated current ( Amps rms ).
Refer to Motor Current Percent in the Feedbacks function. A value of 100% = PMAC rated Current.
PMAC Rated Torque
0558
Same as PNO 555
4.50
0.00 to 30000.00
Nm
ALWAYS
Set the motor’s rated torque.
Refer to Actual Torque in the Feedbacks function. A value of 100% = PMAC Rated Torque.
PMAC Motor Poles
0559
Same as PNO 555
10
0 to 400
ALWAYS
Set the number of motor poles, e.g. for a 4 poles motor enter "4".