D-118 Parameter Reference
AC30 series Variable Speed Drive
Set the motor’s Back EMF line to line, rms value (Ke, Volts rms per 1000 rpm)
Set the motor’s resistance, line to line at 25 °C.
Set the motor’s inductance line to line at maximum current. This parameter is used within the current loop and is related to the overall
proportional gain.
Torque constant (Kt, Nm/A rms).
This parameter is used to compute the current demand given a torque demand :
Torque demand = KT x Current demand
Copper Thermal Time constant(s). If not known set to 300s.
This parameter is used for the motor thermal protection : Refer to Motor Load module.
It represents the time needed to reach 63% of the rated load of the motor if 100% of the rated current is applied to the motor (typical
time constant of a first order low pass filter).