Compliance C-30
AC30 series Variable Speed Inverter
Harmonic Information – AC Supplied Inverters
Supply Harmonic Analysis (Frame D - Normal Duty)
Assumptions: Rsce = 120 at 400V where Q
1n
is the rated rms value of the fundamental voltage of the supply
transformer. The results conform to IEC61000-3-12:2011.
Fundamental Voltage (V)
400
Drive Type
Three Phase
Motor Power
(kW)
1.1
1.5
2.2
3.0
4.0
5.5
1.1
1.5
2.2
3.0
4.0
5.5
Typical Motor
Efficiency %
83
83
83
83
83
83
83
83
83
83
83
83
Harmonic No.
RMS Current (A)
Harmonic No.
RMS Current (A)
1
1.943
2.653
3.946
5.335
7.078
9.694
25
0.064
0.085
0.107
0.140
0.184
0.253
3
0.000
0.000
0.000
0.001
0.001
0.001
27
0.000
0.000
0.000
0.000
0.000
0.000
5
1.479
2.037
2.376
2.573
2.852
3.313
29
0.047
0.067
0.097
0.132
0.175
0.233
7
1.106
1.537
1.636
1.646
1.673
1.745
31
0.037
0.051
0.079
0.107
0.142
0.193
9
0.000
0.000
0.000
0.000
0.000
0.000
33
0.000
0.000
0.000
0.000
0.000
0.000
11
0.406
0.584
0.327
0.446
0.594
0.814
35
0.034
0.046
0.076
0.103
0.135
0.176
13
0.204
0.291
0.354
0.386
0.445
0.558
37
0.030
0.042
0.063
0.086
0.114
0.151
15
0.000
0.000
0.000
0.000
0.000
0.000
39
0.000
0.000
0.000
0.000
0.000
0.000
17
0.153
0.205
0.190
0.259
0.345
0.472
40
0.000
0.000
0.000
0.000
0.000
0.000
19
0.126
0.176
0.167
0.203
0.257
0.349
Total RMS
Current (A)
2.73
3.75
4.92
6.19
7.87
10.47
21
0.000
0.000
0.000
0.000
0.000
0.000
23
0.065
0.088
0.130
0.178
0.236
0.32
* THD (I) %
70.2
70.7
59.8
50.8
43.7
37.8
* (Total Harmonic Distortion)
THD(V) x 100
Q
Q
h
2
1
n
h
40
h
2
%

Table of Contents

Other manuals for Parker AC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 and is the answer not in the manual?

Parker AC30 Specifications

General IconGeneral
Protection RatingIP20
SeriesAC30
TypeVariable Frequency Drive
Overload Capacity150% for 60 seconds
Cooling MethodFan Cooled
Communication ProtocolsCANopen
Power Range0.75 to 250 kW (1 to 350 hp)
Switching Frequency2kHz to 16kHz
SafetySafe Torque Off (STO)
Output CurrentModel Dependent
Power Rating0.75 to 250 kW (1 to 350 hp)
Efficiency>97%
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit, overheating
DimensionsModel Dependent
WeightModel Dependent
Operating Temperature-10°C to +40°C
Output Voltage0 to Input Voltage

Related product manuals