C-29 Compliance
AC30 series Variable Speed Inverter
Frame K:
To access the filter disconnect, first remove the VCM, refer to Chapter 4 for removal instructions. Remove the main cover by unscrewing its 4
fixings (shown on page 4-2), you can then remove the link connection, as highlighted below.
Link CN1 Is the Y-CAP disconnect.
Link CN2 is the VDR disconnect.
The main cover fixings should only be removed once the supply has been disconnected and the residual
energy has been discharged.
“DANGER” – Risk of electric shock. Cover and cover screws must remain in place while drive is energised”,
the EMC filter disconnect will become live once cover and cover screws are removed.
Note: When links are fitted they should be across pins
1 and 4 on the connectors, as shown above.