EasyManua.ls Logo

Parker AC30 - Encoder Slot 2

Parker AC30
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Reference D-57
AC30 series Variable Speed Drive
Encoder Slot 2
Parameters::System Board::Encoder Slot 2
This feature allows you to setup and monitor the operation of the encoder attached to slot 2 of the system board.
Parameter Name
No.
Path
Default
Range
Units
Writable
Encoder Lines
1671
Setup::Inputs and Outputs::SB Encoder
Slot2
Parameters::System Board::Encoder
Slot 2
2048
1 to 100000
STOPPED
The number of lines per encoder revolution
Encoder Invert
1672
Same as PNO 1671
FALSE
STOPPED
Reverses the encoder direction if TRUE.
Encoder Type
1673
Same as PNO 1671
0
0:QUADRATURE
1:CLOCK/DIRECTION
STOPPED
Normally the encoder will be quadrature. Exceptionally, eg if a proximity sensor or other pulse train is used, it needs to be clock /
direction.
High Input Threshold
1674
Same as PNO 1671
FALSE
STOPPED
Changes the threshold level for the encoder pulses between 1.8 V and 6.5 V typical. For encoders powered from 5 V the low theshold
should be used. For other supply voltages the high threshold will provide greater noise immunity.
Encoder Speed
1675
Parameters::System Board::Encoder
Slot 2
RPM
NEVER
The speed measured by the encoder, in revolutions per minute.
Encoder Count Reset
1676
Same as PNO 1671
FALSE
ALWAYS
Resets the encoder count.