EasyManua.ls Logo

Parker AC30 - Page 175

Parker AC30
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ethernet 12-10
AC30 series Variable Speed Inverters
Parameter Name
No.
Path
Default
Range
Units
Writable
Ethernet parameter.
DHCP enable. Set to TRUE to obtain an IP address from the connected DHCP server.
Auto IP
0930
Setup::Communications::Base Ethernet
Parameters::Base Comms:: Ethernet
TRUE
FALSE
TRUE
ALWAYS
Ethernet parameter.
DHCP enable. Set to TRUE to obtain an IP address using Auto-IP.
User IP Address
0933
Setup::Communications::Base Ethernet
Parameters::Base Comms:: Ethernet
0.0.0.0
0.0.0.0 to
255.255.255.255
ALWAYS
Ethernet parameter.
The preferred fixed IP address of the Ethernet.
For the Ethernet to take on this address both DHCP and Auto-IP must be disabled.
User Subnet Mask
0934
Setup::Communications::Base Ethernet
Parameters::Base Comms:: Ethernet
0.0.0.0
0.0.0.0 to
255.255.255.255
ALWAYS
Ethernet parameter.
The preferred fixed subnet mask of the Ethernet.
For the Ethernet to take on this address both DHCP and Auto-IP must be disabled.
User Gateway Address
0935
Setup::Communications::Base Ethernet
Parameters::Base Comms:: Ethernet
0.0.0.0
0.0.0.0 to
255.255.255.255
ALWAYS
Ethernet parameter.
The preferred fixed gateway address of the Ethernet.
For the Ethernet to take on this address both DHCP and Auto-IP must be disabled.
Lock
0936
Parameters::Base Comms:: Ethernet
FALSE
FALSE
TRUE
ALWAYS
Ethernet parameter.
When set to TRUE, this prevents the IP settings being changed via an IP configuration tool. The IP settings may still be modified
from the GKP and the inverter web Parameters page.