C-7 Compliance
AC30 series Variable Speed Inverter
Standard EN 61800-3
Frame G
Frame H
45kW
Frame H
55kW & 75kW
Frame J
132kW
Frame K
250kW
Conducted Emissions
AC Supported Inverters
Category C1
Not suitable for use in this environment
Category C2
When fitted with an EMC filter kit (internal filter, clamping bracket and ferrite)
Maximum cable length 10 m
When fitted with the specified external
filter & EMC filter kit, refer to C17
Maximum cable length 25 m
Please contact Parker
for more information
Category C3
Where I<=100A
When fitted with an internal filter
Maximum cable length 50 m
n/a
Category C3
Where I>=100A
n/a
When fitted with an internal filter
Maximum cable length 50 m
Standard build
Maximum cable length 50 m
DC Supplied
System
Category C3
When supplied by AC to DC full bridge and required line choke. Maximum cable length 50 m.
Not applicable
Radiated
Emissions
When mounted inside a cubicle with the required attenuation between:
Category C1
Not Applicable
Category C2
30-1000MHz at 10dB
Category C3
No specific enclosure required
Cable Requirements
Power Supply
Cable Type
Unscreened
Segregation
From all other wiring (clean)
Length Limit
Unlimited
Motor Cable
Cable Type
Screened/Armoured
Segregation
From all other wiring (noisy)
Screen to Earth
Both ends
Output Choke
300 meters maximum
External Filter
to Drive
Cable Type
Screened/Armoured
Segregation
From all other wiring (noisy)
Length Limit
0.3 meters
Screen to Earth
Both ends
Brake Resistor
Cable Type
Screened/Armoured
Segregation
From all other wiring (noisy)
Length Limit
25 meters
Screen to Earth
Both ends
Signal/Control
Cable Type
Screened
Segregation
From all other wiring (sensitive)
Length Limit
25 meters
Screen to Earth
Drive end only