D-88 Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
DC Inj Timeout
0330
Parameters::Motor Control::Inj Braking
90.000
0.000 to 600.000
s
ALWAYS
Maximum time in the low frequency injection braking state
DC Inj Base Volts
0331
Parameters::Motor Control::Inj Braking
100.00
0.00 to 115.47
%
ALWAYS
Maximum volts applied at base speed
Note: DC injection braking procedure has higher percentage of successful stoppages for the lower power range (frames D-G), than at higher power
range (frames H-K).