EasyManuals Logo

Q2 Q2A User Manual

Q2 Q2A
866 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #182 background imageLoading...
Page #182 background image
5.2 European Standards
182 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
Model Terminal
Recomm. Gauge
mm
2
Applicable Gauge
(IP20 Applicable Gauge
*1
)
mm
2
Wire Stripping
Length
*2
mm
Terminal Screw
Size and Shape
Tightening Torque
Nm (lbfin)
2257
R/L1, S/L2, T/L3 50 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
U/T1, V/T2, W/T3 50 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
-, +1 70 × 2P
35 - 120 × 2P
(120 × 2P)
-
M10
20
(177)
+3 35 × 2P
25 - 70 × 2P
(70 × 2P)
-
M10
20
(177)
95
95 - 240
(-)
-
M10
18 - 23
(159 - 204)
2313
R/L1, S/L2, T/L3 70 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
U/T1, V/T2, W/T3 70 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
-, +1 95 × 2P
35 - 120 × 2P
(120 × 2P)
-
M10
20
(177)
+3 50 × 2P
25 - 70 × 2P
(70 × 2P)
-
M10
20
(177)
95
95 - 240
(-)
-
M10
18 - 23
(159 - 204)
2360
R/L1, S/L2, T/L3 120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
35
(310)
U/T1, V/T2, W/T3 120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
35
(310)
-, +1 120 × 2P
95 - 185 × 2P
(185 × 2P)
-
M12
35
(310)
+3 70 × 2P
50 - 95 × 2P
(-)
-
M12
35
(310)
120
120 - 240
(-)
-
M12
32 - 40
(283 - 354)
2415
R/L1, S/L2, T/L3 120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
35
(310)
U/T1, V/T2, W/T3 120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
35
(310)
-, +1 120 × 2P
95 - 185 × 2P
(185 × 2P)
-
M12
35
(310)
+3 70 × 2P
50 - 95 × 2P
(-)
-
M12
35
(310)
120
120 - 240
(-)
-
M12
32 - 40
(283 - 354)
*1 For IP20 protection, use wires that are in the range of applicable gauges.
*2 Remove insulation from the ends of wires to expose the length of wire shown.
*3 For wire gauges more than 30 mm
2
, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lbf∙in to 40 lbf∙in).
*4 Install an RCM/RCD with this wire gauge to maintain compliance with IEC/EN 61800-5-1:2007.
*5 Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*6 A junction terminal is necessary to connect a braking unit (CDBR-series) to terminals - and +3.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Q2 Q2A and is the answer not in the manual?

Q2 Q2A Specifications

General IconGeneral
BrandQ2
ModelQ2A
CategoryController
LanguageEnglish