Examples for operation of PZD process data area
Example 1
The master communicates with the slave via PPO4. We need set monitoring pa-
rameters corresponding to PZD3 - PZD6, see fig. 13-5 "PPO type" on page 204.
If we need to start frequency converter for forward rotation at 50.00 Hz
(0×1388), and request PZD3 to reflect output current, PZD4 to reflect output
voltage, PZD5 to reflect DC bus voltage, PZD6 to reflect module temperature,
respective parameters are set as: [H0.10]=5, [H0.11]=4, [H0.12]=7, [H0.13]=16.
Complete PPO request and response messages are shown in table below.
PZD1 PZD2 PZD3 PZD4 PZD5 PZD6
PPO request message
CW REF
0x0000 0x0000 0x0000 0x0000
0x0081 0x1388
PPO response message
SW ACT
0x0000 0x0206 0x02DD 0x0019
0xxx02 0x1388
Tab. 13-36: Example 1 for PZD process data area_request and response messages of PPO
The higher byte of the status word is the latest error code (0x00
means no error).
Example 2
When the frequency converter forward runs at 50 Hz, to stop the frequency con-
verter as parameter settings, please refer to example 1.
PZD1 PZD2 PZD3 PZD4 PZD5 PZD6
PPO request message
CW REF
0x0000 0x0000 0x0000 0x0000
0x0088 0x1388
PPO response message
SW ACT
0x0000 0x0000 0x0049 0x0013
0xxx00 0x0000
Tab. 13-37: Example 2 for PZD process data area_request and response messages of PPO
Bosch Rexroth AG
Communication Protocols
EFC 3600
208/259
DOK-RCON03-EFC-3600***-IT03-EN-P