b1.44: Reserved
b1.45 Overexcitation deceleration gain
Setting range 1.00 ~ 1.40
Minimum unit 0.01
Factory default 1.00
b1.46 ~ b1.49: Reserved
Used for the fine tuning of over excitation deceleration to obtain a better level
of over excitation in V/F control mode.
A higher gain will increase the braking capability of overexcitation.
Reduce [b1.45] when the motor slip gets too high, which can trigger overcur-
rent (OC), frequency converter overload (OL-1), or motor overload (OL-2) er-
rors.