The LCD backlight will be inactive automatically if no key has been
pressed for 80 seconds. If the LCD backlight is inactive, the first key
press will activate the backlight, press again to execute the command.
1: Always on
The LCD backlight will be always active.
It is recommended to set the LCD backlight mode to "1: Always
on" when [b1.02] = 1 or 2.
b0.08
LCD display in run mode Factory default 0
Setting range 0...17 Minimum unit 1
b0.09
LCD display in stop mode Factory default 2
Setting range 0...17 Minimum unit 1
0: Output frequency
1: Output rotation speed
2: Set frequency
3: Set rotation speed
4: Output voltage
5: Output current
6: Output power
7: DC bus voltage
8: Torque current
9: Excitation current
10: User-defined reference value
11: User-defined output value
12: Reference torque
13: Digital inputs status
14: Encoder speed feedback
15: Torque limit setting
16: Speed limit setting
17: Multi-monitoring display
When [b0.08] or [b0.09] = 13, "Digital inputs status" is displayed as a decimal
value which represents OPEN or CLOSED of 10 digital inputs X1...X8, FWD
and REV. The value of "Digital inputs status" is 0 to 3377.
For example, if "1234" is displayed to indicate the "Digital inputs status", the
respective status of each digital input is shown as the table below.
DOK-RCON02-FV*********-IB08-EN-P Bosch Rexroth AG 103/259
Rexroth Frequency Converter Fv
Parameter Settings

Table of Contents

Other manuals for REXROTH Fv Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the REXROTH Fv Series and is the answer not in the manual?

REXROTH Fv Series Specifications

General IconGeneral
BrandREXROTH
ModelFv Series
CategoryDC Drives
LanguageEnglish

Related product manuals