EasyManua.ls Logo

REXROTH Fv Series - Page 159

REXROTH Fv Series
262 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The input of PTC / NTC shares the same channel with VR1 or VR2.
Therefore the settings of E4.07 should avoid mutually exclusive settings
as shown below:
When [E4.07] = 1, if settings are as below,
[E3.00] = 1 / 3 or [E3.13] = 1
[E3.00]=1 / 2 or [E3.03] = 2 / 3
[E0.01]...[E0.08] = 18 / 23 / 28
[b1.00] = 2 or [E0.09] = 0 / 3 / 4 / 6
[b1.03] = 2 or [S1.05] = 1
Fv will report fault message "PRSE" after start.
When [E4.07] = 2, if settings are as below,
[E3.00] = 1 / 3 or [E3.13] = 2
[E3.00] = 1 / 2 or [E3.03] = 4 / 5
[E0.01] to [E0.08] = 24 / 29
[b1.00] = 2 or [E0.09] = 1 / 3 / 5
Fv will report fault message "PRSE" after start.
When [E4.07] = 3, if settings are as below,
[E3.00] = 1 / 3 or [E3.13] = 3
[E3.00] = 1 / 2 or [E3.03] = 6 / 7
[b1.00] = 2 or [E0.09] = 7
Motor overheat protection input channel shares the same filter time con‐
stant E0.14 with the analog input channel.
E4.08
Motor over heat reference Factory default 2.0
Setting range 0.0...10.0 V Minimum unit 0.1
When the temperature arrives at the set value of E4.08 (motor overheat
reference), the motor will freewheel stop with fault message "M.O.H."
displayed on the operating panel.
To activate this function, the corresponding motor over heat reference
based on temperature sensor type needs to be calculated. If [E4.06] =
0, [E4.07] = 1, digital inputs +10 V, VR1 and GND are used.
The calculation formula is shown as below:
[E4.08] = 10 V × (R
PTC
//100 k) / [R + (R
PTC
//100 k)]
The wiring diagram of PTC temperature detection is shown as below:
Fig. 7-50: Wiring diagram of PTC temperature detection
DOK-RCON02-FV*********-IB08-EN-P Bosch Rexroth AG 157/259
Rexroth Frequency Converter Fv
Parameter Settings

Table of Contents