Chapter 5 Configuring the PM130 PLUS Configuring Billing/TOU
PM130 PLUS Powermeter Series_Installation Operation and Manual 107
5.4.1 Configuring Billing/Tariff Registers
To configure the billing/TOU registers in your meter:
1. Select Energy/TOU from the Meter Setup menu.
Figure 5-15: Energy/TOU Setup Dialog Box – Billing/TOU Registers tab
2. Configure the register options according to the valid parameters shown in Table 29.
Table 29: Billing/TOU Register Options
Links tariff registers to the selected energy source
Enables recording energy registers in a daily billing profile file (both
total and tariff registers if TOU is enabled).
Enables recording maximum demand registers in a daily billing
profile file (both total and tariff registers if TOU is enabled)
Enables recording total (summary) registers in a daily billing profile
file.
kWh, kvarh, kVAh,
m
3
, CF (cubic foot),
CCF (hundred cubic
feet)
The register measurement units. When a register is linked to an
internal energy source, it is set automatically. When an external
pulse source is used, the user can select a measurement unit for
the register.