Appendix A Technical Specifications Measurement Specifications
PM130 PLUS Powermeter Series_Installation Operation and Manual 152
A.12 Measurement Specifications
Table 33: Measurement Specifications Parameters
Parameter
Full Scale @ Input
Range
Accuracy
Range
%
Reading
%
FS
Conditions
Voltage
120VxPT @ 120V
400VxPT @ 690V
0.2
0.0
2
10% to 120% FS
0 to 1,150,000 V
Starting voltage
1.5-5.0% FS
(selectable)
Line current
CT
0.2
0.0
2
For In = 5A
1% to 200% FS
For In = 1A
5% to 200% FS
0 to 50,000 A
Starting current 0.1%
FS
Active power
0.36PTCT @ 120V
1.2PTCT @ 690V
0.3
0.0
2
|PF| 0.5
3
-10,000,000 kW to
+10,000,000 kW
Reactive power
0.36PTCT@ 120V
1.2PTCT @ 690V
0.3
0.0
4
|PF| 0.9
1
-10,000,000 kvar to
+10,000,000 kvar
Apparent power
0.36PTCT @ 120V
1.2PTCT @ 690V
0.3
0.0
2
|PF| 0.5
1
0 to 10,000,000 kVA
Power factor
1.000
0.2
|PF| 0.5,
I 2% FSI
-0.999 to +1.000
Frequency
50 Hz
60 Hz
25 Hz
400 Hz
0.02
0.04
V
L-N
> 25V
15 Hz to 70 Hz
15 Hz to 70 Hz
15 Hz to 70 Hz
320 Hz to 480 Hz
Total Harmonic
Distortion, THD
V
(I), %V
f
(%I
f
)
999.9
1.5
0.2
THD 1%,
V 10% FSV and V
L-N
> 25V,
I 10% FSI
0 to 999.9
Total Demand
Distortion, TDD,
%
100
1.5
TDD 1%,
I 10% FSI,
V
L-N
> 25V
0 to 100
Active energy
Import & Export
Class 0.5S under conditions as per IEC 62053-
22:2003
0 to 999,999,999 kWh
Reactive energy
Import & Export
Class 0.5S under conditions as per IEC 62053-
22:2003, |PF| 0.9
0 to 999,999,999 kvarh
Apparent
energy
Class 0.5S under conditions as per IEC 62053-
22:2003
0 to 999,999,999 kVAh
3
@ 80% to 120% of voltage FS, 1% to 200% of current FS and frequency 50/60 Hz