Chapter 5 Configuring the PM130 PLUS Configuring Communication Protocols
PM130 PLUS Powermeter Series_Installation Operation and Manual 118
5.6.3 Configuring DNP Class 0 Responses
The most common method of getting static object information from the meter via DNP is to issue a read
Class 0 request. The PM130 allows you to configure the Class 0 response by assigning ranges of points
to be polled via Class 0 requests.
To view or build a DNP Class 0 response message:
1. Select Protocol Setup from the Meter Setup menu and click on the DNP Class 0 Points tab.
2. Select the object and variation type for a point range.
3. Specify the start point index and the number of points in the range. Refer to the PM130 DNP3
Reference Guide for available data points.
4. Repeat these steps for all point ranges you want to be included into the Class 0 response.
5. Click Send to download your setup to the meter.
The factory-set Class 0 point ranges are shown in the picture below.
Figure 5-22: Protocol Setup Dialog Box DNP Class 0 Points Tab