Chapter 5 Configuring the PM130 PLUS General Meter Setup
PM130 PLUS Powermeter Series_Installation Operation and Manual 91
5.2.3 Configuring Digital Inputs
The PM130 PLUS can be provided with four, eight or twelve digital inputs that can be linked to control
setpoints to give an indication on input status change (see Configuring Alarm/Control Setpoints), or can
be linked to general pulse counters to count incoming pulses (see Configuring Counters). They can also
be linked to the Billing/TOU registers to count pulses from external wattmeters or gas and water meters.
Using the Front Display
Select dinP from the main menu. This menu entry appears only if the digital I/O module is plugged into the
meter.
Use the UP and DOWN arrow buttons to scroll to the required digital input.
To select a digital input parameter:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the required parameter.
To change the parameter value:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the required value.
3. Press ENTER to confirm the new parameter setting or press ESC to discard changes. You are
returned to the middle window and can configure other parameters.
To store your new settings:
1. Press the ENTER button when the middle window is highlighted.
2. You are returned to the upper window and can select another digital input or exit the menu.
3. Press ESC to exit the menu.
The available options are shown in Table 23.