EasyManua.ls Logo

Satec PM130 PLUS Series - Appendix G Device Diagnostic Codes

Satec PM130 PLUS Series
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix G Device Diagnostic Codes
PM130 PLUS Powermeter Series_Installation Operation and Manual 172
Appendix G Device Diagnostic Codes
Table 40: Device Diagnostic Codes
Diagnostic
Code
Diagnostic
Message
Description
Reason
2
dAtA
Memory/Data fault
Hardware failure
3
rSt
Hardware watchdog reset
Hardware failure
5
CPU
CPU exception
Hardware failure
6
runt
Run-time software error
Hardware failure
7
tout
Software watchdog timeout
Hardware failure
8
PWr.UP
Power Down/Up
Normal power-up sequence
9
rStrt
Warm restart
External restart via communications or
by firmware upgrade
10
ConF
Configuration reset
Corrupted setup data has been
replaced with the default configuration
11
rtc
RTC fault
The clock time has been lost
13
Lo.bAt
Low battery (with a battery backup unit)
Battery replacement is required
15
EEPr
EEPROM fault
Hardware failure
See Diagnostics Display in Chapter 3 for more information on the PM130 PLUS built-in diagnostics.