Chapter 5 Configuring the PM130 PLUS General Meter Setup
PM130 PLUS Powermeter Series_Installation Operation and Manual 99
5.2.7 Configuring Alarm/Control Setpoints
The PM130 PLUS has an embedded logical controller that can perform different actions in response to
user-defined internal and external events. Unlike a PLC, the meter uses a simplified programming
technique based on setpoints that allows the user to define a logical expression based on measured analog
and digital values that produce a required action.
The meter provides 16 control setpoints with programmable operate and release delays. Each setpoint
evaluates a logical expression with one trigger argument. Whenever an expression is evaluated as “true”,
the setpoint performs a programmable action that can send a command to the output relay, or increment
a counter.
The logical controller provides very fast response to events. The scan time for all setpoints is 1 cycle time
(16.6 ms at 60Hz and 20 ms at 50/400 Hz).
Using the Front Display
Select SEtP from the main menu to enter the setup menu.
Use the UP and DOWN arrow buttons to scroll to the required setpoint.
To select a setpoint parameter:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the required parameter.
To change the parameter value:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the required value.
3. Press ENTER to confirm the new setting or press ESC to discard changes.
4. You are returned to the middle window and can configure another parameter.
To store your new setpoint settings after you configured all setpoint parameters:
1. Press the ENTER button when the middle window is highlighted.
2. You are returned to the upper window and can select another setpoint or exit the menu.
3. Press ESC to exit the menu.
See the table below for the available setpoint options.