E.26
SEL-787 Relay Instruction Manual Date Code 20081022
Modbus RTU Communications
Modbus Register Map
Winding 1 Maximum Phase Time-Overcurrent (WDG1 Max Ph TOC)
348 (R/W) WDG1 TOC ENABLE 0 1 0 448
0=N
1=Y
349 (R/W) PHASE TOC LEVEL A 10 1600 120 0.01 449
350 (R/W) PHASE TOC CURVE 0 9 2 450
0=U1
1=U2
2=U3
3=U4
4=U5
5=C1
6=C2
7=C3
8=C4
9=C5
351 (R/W) PHASE TOC TDIAL 5 1500 300 0.01 451
352 (R/W) EM RESET DELAY 0 1 0 452
0=N
1=Y
353 (R/W) CONST TIME ADDER sec 0 100 0 0.01 453
354 (R/W) MIN RESPONSE TIM sec 0 100 0 0.01 454
Winding 1 Residual Time Overcurrent (WDG1 Res TOC)
355 (R/W) WDG1 RES TOC EN 0 1 0 455
0=N
1=Y
356 (R/W) RES TOC LEVEL A 10 1600 10 0.01 456
357 (R/W) RES TOC CURVE 0 9 2 457
0=U1
1=U2
2=U3
3=U4
4=U5
5=C1
6=C2
7=C3
8=C4
9=C5
358 (R/W) RES TOC TDIAL 5 1500 150 0.01 458
359 (R/W) EM RESET DELAY 0 1 0 459
0=N
1=Y
360 (R/W) CONST TIME ADDER sec 0 100 0 0.01 460
361 (R/W) MIN RESPONSE TIM sec 0 100 0 0.01 461
Winding 1 Negative-Sequence Time-Overcurrent (WDG1 Neq Seq TOC)
362 (R/W) WDG1 NSEQ TOC EN 0 1 0 462
0=N
1=Y
363 (R/W) NSEQ TOC LEVEL A 10 1600 120 0.01 463
Table E.32 Modbus Register Map
a
(Sheet 5 of 38)
Modbus Register
Address
b
Name / Enums Units Min Max Def
Scale
Fa c tor
DeviceNet
Parameter
Numbers