Diagnostics
Display Possible cause Rectification of the error
There is a short-circuit
between the reset
input and another
input or output, or the
reset pulse does not
comply with the
r
equirements.
Check the wiring for cross-circuits.
Or:
Check whether the reset pulse complies with
the requirements (see Fig. 95 on page 143).
# Input signal for an
undefined monitoring
case
# Incorrect sequence on
switching the monito-
ring cases
Check the path of the vehicle.
Or:
Check the operating process of the
monitored machine or system.
If necessary, check the configuration of the
monitoring cases with the aid of the CDS.
# Incorrect operation of
the control inputs
Check the operation of the digital control
inputs.
# Short-circuit on control
inputs A1/2 or in-
correct operation of
A1/2 via EFI
# ! Short-circuit on control
inputs B1/2 or in-
correct operation of
B1/2 via EFI
# Short-circuit on control
inputs C1/2 or in-
correct operation of
C1/2 via EFI
# " Short-circuit on control
inputs D1/2 or in-
correct operation of
D1/2 via EFI
# Incorrect operation of
E1/2 via EFI
Check the wiring, the digital control inputs or
the wiring to the devices connected via EFI.
$ Park/stand-by mode
(see section 4.10.7 on
page 64); the OSSDs
are in the OFF state;
the laser is
deactivated.
No error. Readiness is re-established by
switching to a different monitoring case or
withdrawing the stand-by bit via EFI.