Mounting and installation of the compact control panels
5
180 | 354
Switching variants for monitored alarm and horn outputs with
decoupled load (EN 54)
Figure 91: Switching examples for monitored alarm and horn outputs with decoupled load (EN 54)
Rload Load resistance
Rcable Line resistance
Reol Termination resistor
1 Standard EOL
2 EOL with decoupled load
Switching variants for monitored alarm and horn outputs with load
resistance monitoring (VdS)
Figure 92: Switching examples for monitored alarm and horn outputs with load resistance monitoring
(VdS)
Rload Load resistance
Rcable Line resistance
Rx Additional load resistance
* If necessary
* Adaptation of the load resistance.
You will find detailed information regarding the determination of the resistances for
the monitored outputs in the document Planning 008843.
Rload
+
-
5
6
FireOutput2-
FireOutput2+ +
-
7
8
FireOutput1-
FireOutput1+
X11
Rcable
Reol
Rcable
+
-
5
6
FireOutput2-
FireOutput2+ +
-
7
8
FireOutput1-
FireOutput1+
X11
Rload
Rcable
Rcable
Rx