Mounting and installation of the compact control panels
5
181 |
Building Technologies
5.19.2.11 Connection terminals for the I/O card (RT) in the card cage
The I/O card (↑ RT) FCI2007-A1 determines the PIN assignment of the four
connection terminals in the card cage.
External connections on the card cage using the example of module bus card 1
with the associated connection terminals X11 and X12:
● The external connections of module bus card 2 are on connection terminals
X21 and X22
● The external connections of module bus card 3 are on connection terminals
X31 and X32
● The external connections of module bus card 4 are on connection terminals
X41 and X42
● The external connections of module bus card 5 are on connection terminals
X51 and X52
Depending on the card cage, not all slots may be available for module bus cards
and connection terminals. However, the numbering and assignment of the
connection terminals are identical on all card cages.
Connector Pin Designation Description
X11 1 AL-NO Alarm relay normally open contact (normally open)
2 AL_COM Alarm relay center tap (common)
3 AL_NC Alarm relay ↑ normally closed contact
4 27V2 Supply output (+Vsys)
X12 1 0 V Supply output (–Vsys)
2 FAU_NO Fault relay ↑ normally open contact
3 FAU_COM Fault relay center tap (common)
4 FAU_NC Fault relay normally closed contact (normally closed)
X11 5 RT_Fault+ Output 3 (+) fault output
6 RT_Fault- Output 3 (-) fault output
7 FireOutput 2+
Output 2 (+) can be configured as alarm output or horn
output
8 FireOutput 2-
Output 2 (-) can be configured as alarm output or horn
output
X12 5 FireOutput 1+
Output 1 (+) can be configured as alarm output or horn
output
6 FireOutput 1-
Output 1 (-) can be configured as alarm output or horn
output
7 RE_Response/GPIO1
Programmable input/output / RE response in
accordance with ↑ VdS
8 GPIO2 Input/output programmable
Admissible cable cross-section: 0.14…1.5 mm²