6.26.8 Soiling report
The 'Soiling report' lists the 'Compensation value' of the detectors.
● Create report link [➙ 95]
The following elements are listed for each* detector:
● Device customer text
● Device address path
● Operating years
● Compensation level
● Compensation value:
– 'Normal', no action required
– '100%: Warning, change recommended'
– '150%: Maximum, change required'
● Logical customer text
● Logical address
● Serial no. ("ID-Nr.")
' is not read out in real time. The read
value' in a 'Soiling report' can be up to 15 min old upon creation.
You will find detailed information on functions, connection factors and device
compatibility in document 'List of compatibility'.
* FDA221/241:
150%: Maximum, change required
not supported by the aspirating smoke detectors FDA221 and FDA241. Instead of
a service prompt, a corresponding error message is displayed on the 'Station'.