Extinguishing
Configuring flooding zone control
16
354 | 412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
16.5 Configuring flooding zone control
An 'Extinguishing sector control' element contains causes and effects of the
extinguishing controls for a flooding zone.
Main features and typical
application
Typical event category Event text
1
Contains causes and
effects of the extinguishing
controls for a flooding
zone.
' ----Activation/extinguishing pre-
activated'
'Exting. pre-activ.'
' ----Activation/extinguishing activated' 'Autom. activated'
'Manually activated'
'Ext. activated'
'Mechanical release'
' ----Other extinguishing activation' 'Mechanic. blocked'
'Res. cylinder bank'
'Peripheral device'
'Programmable input'
'Mech.blkd.=no rel.'
' ----Activation/extinguishing flooding' 'Flooding'
' ----Activation/extinguishing released' 'Exting. released'
' ----Activation/extinguishing released,
resettable'
'Rel.ext.resettable'
' --Automatic extinguishing release OFF' 'Autom. ext. OFF'
' --Manual extinguishing release OFF' 'Manual ext. OFF'
' --Other isolation' 'Not ready'
'Interlocked'
'Partially OFF'
'Fire controls OFF'
'Ext. equipment OFF'
'Actuator OFF'
'Alarm devices OFF'
'Device superv. OFF'
' ----Activation/extinguishing emergency
hold'
'Emergency hold'
' ----Activation/extinguishing emergency
abort'
'Emergency abort'
' ----Activation/extinguishing emerg.fct.in
quiet state'
'Quiet->Emerg.hold'
'Quiet->Emerg.abort'
' ----Activation/extinguishing cancelled' 'Not released'
' ----Activation/extinguishing supervision' 'Sensor'
' ----Extinguishing activation fault' 'Loss of agent'
'Incorrect dev.pos.'

Table of Contents