13
298 | 412
Operation of the fire brigade key depot (FSD)
Figure 134: 'FSD', 'Hardware' detail editor
In the 'Hardware' detail editor, there are special settings for the fire brigade key
depot FSD if the checkbox in the 'Operated' field is checked:
● 'Release mode'. You can select when the fire brigade key depot is to be
unlocked:
– 'RT active/confirmed'
– 'Fire alarm or Gas alarm and RT active/confirmed'
– 'RT active/confirmed or RT active/unexpected'
● 'Released by Sabotage ALARM': If the checkmark is placed, the fire
department key depot is additionally unlocked by a sabotage alarm.
The sabotage alarm is triggered by a door contact built into the 'Station'. For
service purposes, the function can be switched off at the ↑ Person Machine
Interface before the 'Station' is opened.
● 'Sabotage contact active upon 'FSD Sabotage'': If the checkmark is placed, the
specific output for notification of an intrusion panel is activated in the event of
an FSD sabotage message.
13.8 EVAC panel [NL]
The EVAC panel is an operating and indication unit for manual evacuation control,
integrated in the ↑ Person Machine Interface of the control panel or remotely
connected via an RS485 interface. The EVAC panel consists of a master and up to
four slaves. Master and slave both have up to ten indicators for the evacuation
zones. Both the universal and two-stage evacuation control are suited to automatic
evacuation.
Creating 'Evac panel'
1. Select 'Operation' > ↑ 'Station' in the task card.
2. Create the 'Evac panel' element for the 'Station'. Link [➙ 68]
a The 'Evac panel' element is created along with the 'Evac master' element.