BACnet device configuration
14
338 | 412
14.8.3 BACnet Notification Class Element
All ↑ stations contain a list of 25 pre-defined entries under 'BACnet Notification
Class element' in the detail editor. Each entry stands for a ↑ BACnet notification
class and has one unique address and one customer text within a station. The
addresses are used in the BACnet object ID as instance numbers. The customer
text provides information on which elements of the application are represented by
this notification class. The internal assignment cannot be changed. The settings
should only be changed according to a ↑ management station integrator's
specification, and only when the behavior of different sub-systems has to be
adapted to a superordinate system.
Address Customer text Address Customer text
1 Areas 14 System
2 Sections 15 UGA
3 Zones 16 ↑ AVC
4 Sensors 17 ↑ IC
5 Control groups 18 Network
6 Controls 19 BACnet client
7 Spare 20 BACnet device
8 Channels (log.) 21 Line Summaries
9 Stations 22 Section Summaries
10 Module/Submodules 23 Control Groups HVAC
11 Lines 24 Controls HVAC
12 Devices 25 Channels (phys.) HVAC
13 Channels (phys.)
Table 18: Notification classes