14
314 | 412
Proceed as follows to define the 'Router' or 'Standby router':
1. Open the 'Global system configuration' > 'FS720 network configuration'>
'Ethernet sub-net' > 'SAFEDLINK sub-net' elements in the tree view of the
'Network' task card.
2. Highlight 'Functions' and open the 'Assign dialog' window.
3. Select 'Router' or 'Standby router' from the list and the reference for the
'Station' you want from the tree.
4. Click on 'Assign'.
a The 'Station' is configured as a router station or ↑ standby router station.
IP addresses for Ethernet and
IP addresses ranging from 192.168.200.0…192.168.200.255 to
192.168.255.0…192.168.255.255 are reserved in FS720 can cannot be used.
14.2.3 Configuring a 'Station' as GAP
also be configured as a router or a standby router; otherwise, local or general
access via the Ethernet port will not be possible.
The GAP station is created by assigning the 'Functions' element to the
'Fx72x/Ethernet' or 'Fx72x/SAFEDLINK' reference.
Proceed as follows to configure the 'Station' as 'GAP' or 'Secondary GAP':
w 'Station' is configured as a ↑ router station or ↑ Ethernet station.
1. Open the 'Global system configuration' > 'FS720 network configuration' >
'Ethernet sub-net' elements in the tree view of the 'Network' task card.
2. Highlight 'Functions' and open the 'Assign dialog' window.
3. Select 'GAP' or 'Secondary GAP' from the list and the reference for the 'Station'
you want from the tree.
4. Click on 'Assign'.
a The 'Station' is defined as 'GAP' or 'Secondary GAP'.