Input/output module FDCIO223 with monitored input/output
12
251 |
Building Technologies
'Activation timeout 'unmanned'':
This setting specifies the duration of the time-out in 'Unmanned operation'. The
time-out is started when the control is activated. After the expiration of the set time,
the sounder is deactivated automatically.
NOTICE
Incorrect cause assignment for '
Activation timeout 'manned'
'unmanned''
The 'Activation timeout 'manned'' / 'Activation timeout 'unmanned'' sounder
property is only evaluated for one 'Area' element in the detection tree or for
elements within one 'Area' element.
w One or more sounders are assigned as 'Control' ↑ element effects.
w The 'Activation timeout 'manned'' property and / or 'Activation timeout
'unmanned'' is active.
● Only assign one 'Area' element or elements from one 'Area' element as the
You will find a description of the properties in the 'Hardware' tab in chapter
'Input/output module FDCIO223 [➙ 131]'.
You can also set the properties in the '
information on input / output module FDCIO223 in document
009122. See chapter 'Applicable documents'.
See also
2 Input/output module FDCIO223 [➙ 131]
2 Applicable documents [➙ 13]
12.11 Input/output module FDCIO223 with monitored
input/output
You can configure the two inputs / outputs of the input / output module FDCIO223
as monitored inputs and / or outputs.
You can assign one monitored input as cause for the following controls:
● 'Fire control'
● 'Universal sounder evac control'
● 'Phased sounder evac control'
You can assign one monitored output as an ↑ effect for the following control:
● 'Fire control'
You will find more information on input / output module FDCIO223 in document
009122. See chapter 'Applicable documents'.
See also
2 Input/output module FDCIO223 [➙ 131]
2 Applicable documents [➙ 13]