10
131 |
Building Technologies
10.3.9 Input/output module FDCIO223
You will find more information on input / output module FDCIO223 in documen
009122. See chapter 'Applicable documents'.
The input/output module FDCIO223 has two inputs/outputs, which can be used as
follows:
● Connection of ↑ collective detector lines
● Connection of sounder lines
● Monitored output
● Monitored input
the product version of your input/output module FDCIO223 is ≥40, you can use
the inputs/outputs in mixed operation, i.e. you can use an input/output module for
two different applications from among the ones listed above. You will find the
product version (ES) on the type plate of the input/output module.
Figure 37: Type plate of input/output module FDCIO223
You will find more information on input/output module FDCIO223 in document
A6V10229261. See chapter 'Applicable documents'.
Setting the properties of the 'Collective/input/sounder/output' element
1. Select the 'Hardware' task card.
2. In the tree view, open the ↑ 'Station' > the ↑ line card > the ↑ loop or the
↑ stub.
3. Open the element 'FDCIO223'.
4. Highlight the element 'Collective/input/sounder/output'.
5. Set the properties you want in the detail editor.
The properties are described in the following sections. Only certain properties are
available, depending on how the element 'Collective/input/sounder/output' is
configured. If the element 'Collective/input/sounder/output' is configured as a
↑ collective detector line, for example, then you can only set the properties in the
range 'Collective line'. The other properties are grayed out.
Figure 38: Properties in the detail editor of the ↑ physical channel of the input / output module
FDCIO223
Siemens Switzerland Ltd.
Fire Safety & Security Products
FDCIO223
S24218-B102-A1 40
EN54-18:2005
EN54-17:2005
IdNr.
SW-Vers.
Swiss Made