EasyManua.ls Logo

Siemens FS720 - Additional Criteria for Pre-Stage and Main Stage

Siemens FS720
412 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
'Detec
tion' task card
Configuring the 'Zone'
11
167 |
412
Building Technologies
A6V10210424_j_en_
--
Fire Safety
2018
-
-
29
3. Select 'Two-zone dependency' at the left in the window.
a The 'Detection tree' is depicted at the right of the window. The elements
that can be assigned are highlighted.
4. Select the second 'Zone' for the two-zone dependency.
5. Click on 'Assign'.
a The two 'Zones' are assigned to each other.
See also
2 Creating 'Detection tree' [ 141]
11.5.4 Additional criteria for pre-stage and main stage
Figure 57: Additional criteria for reaching the pre-stage or the main stage, respectively
In the detail editor of the 'Zone', you can define additional criteria for the settings
'Criteria PRE-STAGE' and 'Criteria MAIN STAGE' with the property 'Additional
criteria for PRE-/MAIN STAGE'. It can thus be ensured that 'PRE-STAGE' or 'MAIN
STAGE' will be reached with multi-detector dependency or two-zone
dependency, even in certain situations. The situations and settings are described
in the following sections.
Multi-detector dependency
'Fallback to single detector/zone dependency':
If the number of detectors is no longer sufficient in normal operation, a switch
is made to single-detector dependency in order to fulfill the multi-detector
dependency that has been set, e.g., in the event of a fault or when a detector
has been isolated. If this is the case, then 1 detector with danger level 2 or 3
is sufficient to trigger 'PRE-STAGE' or 'MAIN STAGE'.
The chronological order of the events is not relevant, i.e., a switch is made to
single-detector dependency with both of the following variants:
First, danger level 2 or 3 is reached. Afterwards, the number of detectors
becomes less than required.
First the number of detectors becomes less than required. Afterwards
danger level 2 or 3 is reached.
'TRVB S123: Danger level(s) + fault(s) and/or isolation(s)':
Faults and isolations of the detectors are evaluated in addition to the danger
levels as criteria for reaching 'PRE-STAGE' or 'MAIN STAGE', respectively.
When a danger level is reached and a fault and/or an isolation is reported in
addition, then 'PRE-STAGE' or 'MAIN STAGE', respectively, is reached.
The chronological order of the events is not relevant, i.e., 'PRE-STAGE' or
'MAIN STAGE' is reached with both of the following variants:
First, a danger level is reached. Afterwards a fault and/or an isolation is
reported.
First, a fault and/or an isolation is reported. Afterwards, a danger level is
reached.

Table of Contents

Other manuals for Siemens FS720

Related product manuals